Download PTU M.Tech. EE 1st Semester 70733 ADVANCED RELAYING AND PROTECTION Question Paper

Download PTU. I.K. Gujral Punjab Technical University (IKGPTU) M.Tech. EE 1st Semester 70733 ADVANCED RELAYING AND PROTECTION Question Paper.

1 | M-70733 (S9)-2382

Roll No. Total No. of Pages : 02
Total No. of Questions : 08
M.Tech.(Power System) (2013 & Onwards) (Sem.?1)
ADVANCED RELAYING AND PROTECTION
Subject Code : MTPS-104
M.Code : 70733
Time : 3 Hrs. Max. Marks : 100

INSTRUCTIONS TO CANDIDATES :
1. Attempt any FIVE questions out of EIGHT questions.
2. Each question carries EQUAL marks.

1. A 30 MVA, 11.5 Kv, star- delta power transformer is to be protected by differential
protection. The high voltage side phase lags behind low voltage side phase by 30?.
Formulate the complete differential protection for the transformer by selecting CT ratios,
CT connections. The continuous current carrying capacity of restraining coils of the
differential relay should not exceed 5 Amp. CT ratio is 3000/5 on 11.5 Kv side.
Determine CT ratio on 69 kV side.
2. Show in detail, the protection arrangement of a 60MW generator provided with :
a) Differential protection
b) Back-up over current protection through faults
3. Explain the functions and common features of SCADA in integrated and multifunction
protection scheme in power sector.
4. State the various applications of over current relaying. Distinguish between inverse
characteristics and definite characteristics.
5. What are the merits of carrier current relay? Where is it used? Compare pilot wire
relaying with carrier current protection.
6. Explain the scheme of pilot wire relaying employed :
a) Circulating current method
b) Voltage balanced method
FirstRanker.com - FirstRanker's Choice
1 | M-70733 (S9)-2382

Roll No. Total No. of Pages : 02
Total No. of Questions : 08
M.Tech.(Power System) (2013 & Onwards) (Sem.?1)
ADVANCED RELAYING AND PROTECTION
Subject Code : MTPS-104
M.Code : 70733
Time : 3 Hrs. Max. Marks : 100

INSTRUCTIONS TO CANDIDATES :
1. Attempt any FIVE questions out of EIGHT questions.
2. Each question carries EQUAL marks.

1. A 30 MVA, 11.5 Kv, star- delta power transformer is to be protected by differential
protection. The high voltage side phase lags behind low voltage side phase by 30?.
Formulate the complete differential protection for the transformer by selecting CT ratios,
CT connections. The continuous current carrying capacity of restraining coils of the
differential relay should not exceed 5 Amp. CT ratio is 3000/5 on 11.5 Kv side.
Determine CT ratio on 69 kV side.
2. Show in detail, the protection arrangement of a 60MW generator provided with :
a) Differential protection
b) Back-up over current protection through faults
3. Explain the functions and common features of SCADA in integrated and multifunction
protection scheme in power sector.
4. State the various applications of over current relaying. Distinguish between inverse
characteristics and definite characteristics.
5. What are the merits of carrier current relay? Where is it used? Compare pilot wire
relaying with carrier current protection.
6. Explain the scheme of pilot wire relaying employed :
a) Circulating current method
b) Voltage balanced method
2 | M-70733 (S9)-2382

7. Explain the importance of testing of relay. Describe the following terms of relays :
a) Plug setting
b) Time setting
8. Explain the functions of the following components in microprocessor based relay :
a) Buffer
b) Program memory
c) Data memory
d) ALU
e) Control and timing unit
f) Clock
g) Register









NOTE : Disclosure of Identity by writing Mobile No. or Making of passing request on any
page of Answer Sheet will lead to UMC against the Student.