GUJARAT TECHNOLOGICAL UNIVERSITY
BE - SEMESTER-V (OLD) EXAMINATION - WINTER 2018
--- Content provided by FirstRanker.com ---
Subject Code:150902 Date: 07/12/2018Subject Name: Power System Analysis And Simulation
Time: 10:30 AM TO 01:00 PM Total Marks: 70
Instructions:
- Attempt all questions.
- Make suitable assumptions wherever necessary.
- Figures to the right indicate full mark.
--- Content provided by FirstRanker.com ---
Q.1 (a) A 230-kV, 60 Hz three-phase transmission line is 80 km long. The per phase 07 series impedance and shunt admittance of the line are z = 0.05 +j0.45 Q per km and y = j3.4 x 10 siemens per km respectively. The line delivers 200 MVA at 0.8 lagging power factor at 220 kV. Using the nominal © model, determine: (a) The transmission line ABCD constants. b) Sending end voltage and current c) Voltage regulation, d) Sending end power ¢) Transmission efficiency.
(b) A20MVA, 6.6 kV, 3-phase star-connected alternator having a reactance of 25% 07 is connected through a 10 MVA, 6.6 kV/33 kV transformer of 15% reactance to a transmission line having a resistance and reactance per conductor per kilometer of 0.25 Q and 1.2 Q respectively. 70 kilometers along the line, a short circuit occurs between the three conductors. Find the current fed to the fault by the alternator.
Q.2 (a) For a long transmission line, using rigorous solution method, obtain the 07 expressions relating sending end and receiving end voltages and currents and expressions for A,B,C,D constants for long transmission Line.
--- Content provided by FirstRanker.com ---
(b) The line currents in three phase unbalanced(system are [rR=(12 +j6) A, Iy=(12 07 —j12) A and Ig=(-15 + j10) A. The phase sequence is RYB. Calculate the positive, negative and zero sequence components of currents.
OR
(b) Draw an impedance diagram for the electric power system shown in Fig. 1, 07 showing all impedances in per unit on a 100-MVA base. Choose 20 kV as the voltage base for generator Gi.
The three-phase power and line-line ratings are given below:
--- Content provided by FirstRanker.com ---
Gi: 90 MVA 20kV X=9%T1: 80 MVA 20/200 kV X=16%
T2: 80 MVA 200/20 kV X =20%
G2: 90 MVA 18 kV X=9%
Line: 200 kV X=120Q
--- Content provided by FirstRanker.com ---
Load: 200 kV S =48 MW + j64 MvarQ.3 (a) Draw and explain various transformer connections and their zero sequence 07 networks. In the diagrams of transformer connections, clearly show the current paths through the transformer windings and through ground terminal wherever applicable.
(b) With reference to Z- bus building algorithm, explain the type-1, the type-2 and type-3 modifications with necessary equations.
OR
--- Content provided by FirstRanker.com ---
Q.3 (a) Explain sub-transient, transient and steady state reactances of synchronous machine and draw the machine circuit models using them.
Q.4 (b) A 3-phase transmission line, operating at 11 kV and having a resistance of 1.5 Q and reactance of 6 Q, is connected to the generating station bus-bars through 5 MVA step-up transformer having a reactance of 5%. The bus-bars are supplied by a 12 MVA alternator having 25% reactance. Take 12 MVA as base MVA. Calculate the short circuit MVA fed to symmetrical fault between phases if it occurs:
a) at the load end of transmission line;
b) at the high voltage terminals of the transformer.
Q.4 (a) Explain the operation principle of resonant grounding with suitable line diagram and phasor diagram. Derive the expression for inductance of arc suppression coil for resonant grounding.
--- Content provided by FirstRanker.com ---
(b) Write a short note on selection of circuit breakers.
OR
Q.5 (a) If value of impedance is given in ohm, derive
This download link is referred from the post: GTU BE/B.Tech 2018 Winter Question Papers || Gujarat Technological University
--- Content provided by FirstRanker.com ---